ICS Primary Data Center
Vital Statistics: December 2024 Census
Size: 1600 sqft
HVAC: 3 Units
Cabinets: 42
Servers (~800)
Bare Metal: 598
Virtual Machines: 300
-
Servers: 20
Petabytes: 3.2 PB
Network (locally managed, 1/10/40GB)
GPU
Clusters: 8
GPU hosts: 44
Distributed computing managed by
Slurm
Requirements for Equipment inside Data Center
Please use the following checklist to make sure equipment can be hosted in the ICS Data Center:
All ICS faculty and researchers are welcome to place their equipment in the ICS data center so long as the equipment has the following attributes:
Rack mountable: The equipment must rack neatly and securely into a standard 19“ cabinet. Rack mount kit is required.
Advanced Out of Band Management: Often called BMC, iDRAC, IPMI, ILOM, or OOB, out of band management should provide complete remote administration with a full console.
Trusted Platform Module (TPM): We are encrypting Linux installs and the module allows the passphrase to be saved there to be used for autoboot.
Airflow: The ICS data center is split into hot and cold aisles. Any equipment in the data center must take cold air in from the cold aisle and exhaust into a hot aisle. Typically, the means front to back airflow.
Proper Form Factor: Equipment must actually fit in a standard rack or a specialty rack must be provided. Typically, this means the equipment must have a depth of 30” or less.
IPv4: The equipment must be capable of using an IPv4 address. At this time we do not offer IPv6 addresses.
Power Supply Cables: The standard power cord is C13-C14. There are a limited number of C19-C20 connections in the datacenter.
Additional Requirements for Managed Equipment
ICS Computing support can manage equipment that comes assembled, is certified for the intended OS, and includes a minimal warranty. ICS researchers are welcome to house any system that meets the basic requirements and self-support but we are unable to provide support for self assembled or DIY builds.
Provided
The following resources are provided by ICS free of charge for all equipment in the ICS data center:
Up to 2 120V or 240V power connections per host.
Up to 2 1Gb/s per node plus 1 OOB connections.
Space in cabinet limited by availability and heat restrictions.
Recommended
The following lists out additional recommendations for servers in the ICS Datacenter:
RAID 10/5/6 support.
Redundant PSU
10Gb/s Network
5 year NBD warranty
Required for ICS Managed Systems
Equipment Purchase Workflow
ICS Support can help get server quotes after being provided system specifications.
Servers are reviewed for:
Chassis depth and height.
Maximum power usage (applies especially for GPU servers)
Power input cord (C13 or C19). We have been surprised with C19 which we have less outlets for.
Network requirements (10GB, 1GB, fiber, etc)
Minimum 3 years warranty, with 5 years preferred.
A helpdesk ticket should be open with the quotes included for customer/ICS review and approval.
Installation Workflow
Create IP address with name chosen for the server
Rack server and install.
Test max power consumption of server.
Re-rack if necessary or add more power to rack if available.
We can look up purchase orders in KFS to determine what equipment a property tag is meant for:
-
Click on “Finances/KFS” menu link and then the KFS Homepage under the “Tools & Support” section.
Click on “Custom Document Search” and click on “Search - Purchase Orders”.
Click on the heart icon to make it a favorite so you can see the it from the Home link.
For the search, just enter the purchase order number in the “Purchase Order #” field.
The search results will be at the bottom of the page.
CRAH Units
CRAH Maintentance
Motor Replacement
Motors on all three units were replaced by campus facilities in the first half of 20222. Lifetime on the motors is projected to be 12 years. We'll need to look at replacing them again in 2034.
Portable AC Units
ICS purchased 3 portable AC units with BSAS funding.
Name | Original Name | MAC | Location | Last Known IP | SwitchPort | Observium |
Moe | poweralert-00066745cc57 | 00:06:67:45:cc:57 | N06 | | B12/3023-C2950S-085/3 | 114 |
Larry | poweralert-00066745cc50 | 00:06:67:45:cc:50 | A13 | 10.195.255.251 | C1/3023-C2950G-046/7 | 116 |
curly | poweralert-00066745cc51 | 00:06:67:45:cc:51 | H04 | 10.195.255.252 | A04/3023-C2950G-045/14 | 115 |